ALL IN ONE 2 | AC COUPLED
All in One 2, MPPT Unit, Gateway 2, Expansion Battery User Manual
GIV-AIO-AC-6.0/8.0/10.0/11.0/12.0,
GIV-BAT-13.5-AIO2, GIV-MPP-20.0-G1,
GIV-AIO-GW1-2, GIV-BAT-13.5-AIO2-E
V1 OCT 25
CONTENTS
- SAFETY – Safety Symbols Description; General Safety; Electrical Safety (Grounding Requirements; PV String Side Operation; Inverter Requirements; AC Side Operation)
- PRODUCT DESCRIPTION – Introduction (System Components); System Diagrams; All in One 2 (Interface Description; Specification); MPPT Unit (Interface Description; Specification); Expansion Battery (Interface Description; Specification); Gateway 2 (Interface Description; Specification); Key Features; Inverter Operating Modes; Main Work Modes (Daytime Mode; Night-time Mode; Island Mode; Demand Response Mode)
- INSTALLATION – Unpacking Inspection; Packaging List (All in One 2; Gateway 2; MPPT Unit); Safety Instructions; Mounting Area; Installation Procedure (All in One 2 and MPPT Unit (Desk); Gateway 2); Electrical Connection (Desk AC Connection; Gateway 2 AC Connection); Communication Connection (System Communication Connection; Gateway 2 Communication Port; All in One 2 Communication Port; Wireless Communication; DRM (Demand Response Management))
- SYSTEM COMMISSIONING – Pre-Commissioning Checks; System Startup and Shutdown (Start-Up the Inverter; Disconnect the Inverter (Shutdown); Equipment Parameter Setting and Monitoring)
- MAINTENANCE – System Power-Off for Maintenance; Regular Maintenance
- TROUBLESHOOTING – Troubleshooting
- SYSTEM REMOVAL AND DISPOSAL – Remove Machine; Scrap Machine (Disposal)
LEGAL INFORMATION
Warning Notice System
This manual contains important safety notices to ensure your personal safety and prevent damage to property. These notices are identified by specific symbols and are categorized according to the severity of the potential hazard. Please read and follow these warnings carefully.
![]() | DANGER Indicates an immediate hazard that will result in severe injury or death if not avoided. It’s the highest level of risk. |
![]() | WARNING Indicates a potential hazard that could result in serious injury or death if not avoided. It’s slightly less severe than “Danger.” |
![]() | CAUTION Indicates a potential hazard that could result in minor injuries or property damage if not avoided. |
![]() | NOTICE Used to provide additional, helpful information. It doesn’t indicate hazards. |
Qualified Personnel
The GivEnergy All in One described in this manual must only be installed and maintained by qualified personnel. Qualified personnel are individuals who have received training in electrical systems and photovoltaic (PV) installations (not required for AC Coupled only installations) are familiar with local electrical codes and regulations, and are able to identify risks and avoid potential hazards associated with handling high-voltage equipment.
![]() | WARNING
|
SAFETY
Safety Symbols Description
![]() | DANGEROUS VOLTAGE The product works with high voltage. Only qualified tradespeople must do work on the product. They must follow the product’s documentation. |
![]() | HOT SURFACE The product can get hot when it works. Do not touch the product when it is working. |
![]() | OBSERVE OPERATING INSTRUCTIONS Read the product’s documentation before you work on it. Follow all safety precautions and instructions in the documentation. |
![]() | GROUND PROTECTION Shows the connection point for grounding protection. |
![]() | DIRECT CURRENT (DC) |
![]() | ALTERNATING CURRENT (AC) |
![]() | ELECTRIC SHOCK RISK (5 MINUTES) Signals danger from electric shock. It shows the time (5 minutes) to wait after the inverter is off and disconnected. This ensures safety in any installation operation. |
![]() | CE MARK The inverter meets the requirements of applicable CE guidelines. |
![]() | DO NOT DISPOSE WITH HOUSEHOLD WASTE The Hybrid inverter must not be disposed of with household waste. |
General Safety
The GivEnergy All in One system is a high-voltage device. Incorrect installation, handling, or maintenance can cause serious injury, death, or equipment damage.
To ensure safe operation, always follow the guidance below:
- Please read this document carefully to understand the products and precautions before installing the device. The terms “caution”, “warning”, and “danger” in the manual do not represent all safety precautions to be observed, but only supplement all safety precautions.
- All equipment operations must be carried out by professional and qualified electrical technicians. They must be familiar with the relevant standards and safety specifications of the project location.
- When the inverter is operated, it is necessary to use insulating tools and wear personal protective equipment to ensure personal safety.
- When contacting electronic devices, wear electrostatic gloves, electrostatic bracelets, and anti-static clothing to protect the inverter from electrostatic damage
- It is strictly forbidden to install, use, and operate outdoor equipment and cables in bad weather such as lightning, rain, snow, and high winds. This includes but is not limited to handling equipment, operating equipment and cables, plugging and unplugging signal interfaces connected to outdoors, working at height, and outdoor installation.
- Please follow the requirements of this manual. Use the correct tools and master the correct use of the tools. Please follow the warning signs, warnings, and protective measures on the equipment.
- It is forbidden to carry out installation, wiring, maintenance, and replacement operations with electricity on. Safe isolation procedures must be completed, to confirm that there is no risk of electric shock, while conducting maintenance on the equipment
- When transporting, turnover, installation, wiring, and maintenance, etc., it must meet the laws and regulations and relevant standards of the country and region where it is located.
- The materials provided by the user and the tools required during operation must meet the requirements of the laws, regulations, and relevant standards of the country and region where they are located.
- Do not disassemble the system equipment at will.
For additional safety and warranty information, visit the official GivEnergy website.
Electrical Safety
Grounding Requirements
Equipment must be grounded. When installing, you must first install a protective earth wire. When removing equipment, the protective ground wire must be removed last. The grounding of the energy storage inverter meets the local requirements for the grounding of photovoltaic modules and energy storage inverters. This is to ensure continuous conduction with the ground in order to optimally protect the system and personnel.
![]() | CAUTION
|
PV String Side Operation
Please use the MC4 connectors supplied with the box to connect the inverter DC cable. Using other models of MC4 connector can cause overheating of the connections and invalidate the warranty.
It is recommended that the panel string be connected to the equipment to add a DC isolator. Before the electrical connection of the equipment, if it may encounter a live part, the DC isolator should be in the off position. Only when the MC4 connections are all correct, shall the DC isolator be turned on.
Ensure correct polarity of the DC cable to ensure that the positive and negative poles are correct and there is no reverse connection. Ensure the voltage is within the permissible range. Reverse polarity will cause overcurrent and damage to the equipment.
The unit is a transformerless inverter. It has no galvanic isolation. Do not ground the DC circuit of the PV modules to the inverter. Ground only the mounting frame. If you bond PV modules to the inverter, you will receive an error message “PV ISO is low”.
PV modules with large land capacity, such as thin-film PV modules with cells on metal substrates, can only be used if their coupling capacity does not exceed 470nF.
During feed-in operation, leakage current flows from the battery to the earth. The magnitude of which depends on how the PV modules are installed (e.g., foil on a metal roof) and the weather (rain, snow). This “normal” leakage current should not exceed 30mA, as the inverter will automatically disconnect from the grid as a protective measure.
To disassemble, unplug, and maintain the inverter DC string terminal wire, it must be confirmed that the equipment switch, and the corresponding breaking device of the previous stage are disconnected. Confirm that the equipment and machine are stopped and there is no work.
![]() | DANGER
|
Inverter Requirements
Ensure that the voltage and frequency of the grid supply are correct for the equipment being installed.
It is recommended that the AC power grid add an isolation device to the equipment. The inverter AC side must have overcurrent protection suitable for the inverter being installed.
The specifications of the protection device should be greater than 1.25 times the maximum current of the inverter AC output.
![]() | DANGER - LETHAL VOLTAGE
|
![]() | WARNING - HOT SURFACE
|
AC Side Operation
Please connect the wire L/N/PE on the AC side of the single-phase inverter equipment according to the instructions in this manual. Incorrect connection of the wire sequence may cause damage to the equipment and cause leakage and electric shock.
The AC wire must be disconnected by the corresponding isolation device of the previous stage before being connected to the equipment. Do not short circuit the AC line.
Disassembling, unplugging, and maintaining the AC connection wires of the inverter must confirm that the power is disconnected from the grid. Confirm that the equipment and inverter are powered off and not working.
![]() | DANGER - LETHAL VOLTAGE
|
PRODUCT DESCRIPTION
Introduction
The GivEnergy All in One 2 (AIO2) is a fully integrated energy solution combining a bi-directional inverter and a 13.5kWh battery. The system is designed for energy storage, solar integration, and flexible load management.
The system supports:
- Multi-channel PV input via the MPPT Unit (6 PV channels).
- Smart load and grid management through the Gateway 2.
- Optional capacity expansion using external batteries.
The GivEnergy All in One system supports advanced energy management for residential applications. It can charge its internal battery during off-peak periods when electricity is cheaper and discharge stored energy during peak-rate times to reduce electricity bills.
When used with the Gateway 2, the system enables full home backup during power outages by supplying critical, general, and smart loads. The Gateway 2 manages load prioritisation, generator integration, and grid connection based on user-defined settings.
When connected to the MPPT Unit, the system can receive energy from up to six high-power solar input channels. This supports flexible rooftop PV configurations and maximises solar energy harvesting throughout the day.
The system is scalable through the addition of one or more expansion batteries (up to 2 additional batteries), the total storage capacity increases. This allows the All in One to store more surplus energy and deliver extended power during outages or high-demand periods.
Together, these components form a modular smart energy platform that supports grid-tied, off-grid, and hybrid operation.
The following diagram shows an example smart home energy system using the All in One 2, MPPT Unit, and Gateway 2:
BASIC SYSTEM LAYOUT

SYSTEM WITH EXPANSION BATTERIES AND MULTI-LOAD CONTROL

System Components
When used with Gateway 2, the system can form a multifunctional smart power system including:
- PV Inverter: The PV inverter can be connected to the system as an additional power generation device to make full use of clean energy. Excess energy can be charged to the AIO2 and even discharged to the grid to obtain maximum benefits.
- Off-grid: When AIO2 power is higher than 90%, will automatically turn off the output of the PV inverter. When AIO2 power is lower than 90%, AIO2 will turn on the output of the PV inverter again.
- On-grid: Excess energy can either charge the AIO2 or discharge to the grid. At this time, the AIO2 will not shut down the output of the PV inverter to maximize the benefits.
- EV Charger: The system can be connected to the household electric vehicle chargerto monitor the charging status of electric vehicles in real time.
- Generator: A generator can connect as an extra power source. If the grid is off and the AIO2 power is low, Gateway 2 remotely starts the generator. The generator then powers the system and charges the AIO2. You can set a start state of charge (SOC) for the generator via the Gateway 2 server. If AIO2 power drops below this start SOC, Gateway 2 activates the generator. When the AIO2 battery reaches a “cut-off SOC”, Gateway 2 stops the generator. Grid power always has priority; if the grid returns, Gateway 2 shuts down the generator. You can manually start the generator if grid power is off and the AIO2 battery is extremely low.
![]() | NOTICE
|
- Smart Load: Smart load is one of the household loads. It is recommended to access electrical equipment that consumes a relatively large amount of power and does not need continuous use, such as water heaters. When the system energy supply exceeds the demand, and energy begins to flow into the grid and is greater than 1kW, the smart load begins to work. The smart load will not stop working until the system energy demand is greater than the supply. When the smart load is required in an emergency, the Gateway 2 server provides the facility to forcibly enable or disable the smart load, ensuring that the load can be met at any time.
- Critical Load: Critical load is one of the household loads. It is recommended to access important electrical equipment that requires continuous use, such as network routers, computers, indoor lights, telephones, etc,. When the system has any power supply, the critical load will always be on, and the continuous and stable work of the important load will be guaranteed at all times. Note: This applies only if there is sufficient battery capacity available when off-grid.
- General Load: General load is one of the household loads. It is recommended to access electrical equipment that consumes a relatively large amount of power and is frequently used, such as air conditioning and heating equipment. General load will always be enabled while on-grid.
- The Gateway 2 contains a bypass breaker, to force the load to connect with grid, to bypass the gateway. Only to be used when the system is not functioning.
- Off-grid: When the AIO2 battery SOC is lower than the set value, the general load stops working until the SOC is higher than the set value. Reserving energy for the critical loads.
- When the general load is required in an emergency, the Gateway 2 server provides the button to forcibly enable or disable the general load, ensuring that the load can be met at any time.
System Diagrams
The All in One 2 system supports various configurations. Each diagram below shows a different system layout based on connected components and use cases.
Single All in One 2 System Block Diagram
This configuration includes a standalone All in One 2 unit connected to the grid, a PV inverter, an EV charger, and load circuits via a switchboard.

Single All in One 2 with MPPT Unit Block Diagram
This layout adds rooftop solar PV connected to the MPPT Unit, providing high-input solar capability.

All in One with Gateway 2 System Block Diagram
This setup includes the Gateway 2 for managing smart, critical, and general loads. A generator and EV charger are also connected.

All in One 2, MPPT Unit, and Gateway 2 System Block Diagram
This full-system layout shows All in One 2 connected to the MPPT Unit and Gateway 2. The system supports solar, generator, EV charging, and smart load management.

All in One 2
Interface Description

| Item | Description | Item | Description |
|---|---|---|---|
| A | Communication Port | D | Battery Breaker |
| B | Reserved Port | E | All in One 2 Power Button |
| C | All in One AC Port | F | Front Panel LEDs |
Specification
| Model | GIV-AIO-AC-13.5-6.0 | GIV-AIO-AC-13.5-8.0 | GIV-AIO-AC-13.5-10.0 | GIV-AIO-AC-13.5-11.0 | GIV-AIO-AC-13.5-12.0 |
|---|---|---|---|---|---|
| Internal Battery | |||||
| Battery Type | LFP | ||||
| Operating Voltage Range | 260-346 Vd.c. | ||||
| Nominal Voltage | 307.2 Vd.c. | ||||
| Max. Charging Current | 25A | ||||
| Max. Discharging Current | 41A | ||||
| Max. Charging Power | 6000W (12000W with expansion) | ||||
| Max. Discharging Power | 12600W | ||||
| Battery Capacity | 13.5kWh | ||||
| Output Data (AC, On-Grid) | |||||
| Rated AC Output Power | 6000W | 8000W | 10000W | 11000W | 12000W |
| Max. Apparent Power | 6000VA | 8000VA | 10000VA | 11000VA | 12000VA |
| Nominal Off-Grid Power | 12000VA | 12000VA | 12000VA | 12000VA | 12000VA |
| Peak Power (10s, Off-Grid) | 14400VA | ||||
| Rated/Max. Output Current | 26A | 34.8A | 43.5A | 47.8A | 52A |
| Nominal Grid Voltage/Range | 230 V.a.c (180 to 270V.a.c) | ||||
| Nominal Frequency/Range | 50/60Hz; ±5Hz | ||||
| Power Factor (@Full Load) | >0.99 | ||||
| Power Factor Range | 0.8 lagging - 0.8 leading | ||||
| THDI (@Rated Power) | <3% | ||||
| AC Output Type | Single-Phase | ||||
| General Data | |||||
| Battery Max.Charging/ Discharging Efficiency | 96.5% | ||||
| PV Max. Efficiency | 97.1% | 97.1% | 97.3% | 97.3% | 97.5% |
| Euro Efficiency | 96.6% | 96.6% | 96.8% | 96.8% | 97.0% |
| MPPT Efficiency | 99.9% | ||||
| Protection Degree | IP65 | ||||
| Protection Class | Class I | ||||
| Overvoltage Category | PV: II, Battery: II, AC: III | ||||
| Inverter Topology | PV: Transformer-less; Battery: Transformer-less | ||||
| Noise Emission (Typical) | 50dB | ||||
| Operation Temperature | -20ºC ~ +50ºC | ||||
| Relative Humidity | 0~100%, Non-Condensing | ||||
| Altitude | 4000m (Derating above 2000m) | ||||
| Dimensions (WxHxD) | 600W*950H*280D (mm) | ||||
| Self-Consumption | <15W | ||||
| Number of Parallel Operation | 2 | ||||
| Display | LED & APP | ||||
| Communication | RS485/WIFI/4G Inside | ||||
| Warranty | 15 Years | ||||
| Monitoring Data | |||||
| Radio Type | 2.4G WiFi / BLE | ||||
| Frequency Range | 2412-2472 MHz For WiFi 2402-2480 MHz For BLE | ||||
| Transmit Power (EIRP) | WiFi: 17.68 dBm (EIRP) BLE: 2.41 dBm (EIRP) | WiFi: 15.46 dBm (EIRP) BLE: 3.02 dBm (EIRP) | |||
| Radio Type | LTE/GNSS | ||||
| Frequency Range | Band 1: 1920-1980 MHz; Band 3: 1710-1785 MHz, Band 7: 2500-2570 MHz; Band 8: 880-915 MHz; Band 20: 832-862 MHz; Band 28: 703-748 MHz; GNSS: 1559-1610 MHz | ||||
| Transmit Power (EIRP) | LTE Band 1/3/7/8/20/28: 23 dBm | ||||
Radiation Exposure Statement: This equipment complies with radiation exposure limits for uncontrolled environments. To ensure safety, it should be installed and operated with a minimum distance of 20 cm between the antenna and your body.
MPPT Unit
Interface Description

| Item | Description | Item | Description |
|---|---|---|---|
| A | PV1+ Port | I | PV6+ Port |
| B | PV2+ Port | J | PV4- Port |
| C | PV3+ Port | K | PV5- Port |
| D | PV1- Port | L | PV6- Port |
| E | PV2- Port | M | PV1/2/3 Isolation |
| F | PV3- Port | N | PV4/5/6 Isolation |
| G | PV4+ Port | O | Grommet Port |
| H | PV5+ Port |
Specification
| Model | GIV-MPP-20.0-G1 |
|---|---|
| Input Data (PV) | |
| Max. DC Input Power | 20,000W |
| Max. DC Input Power of Single MPP Tracker | 4,500W |
| Start-up Voltage | 60V |
| Max. PV Open-Circuit Voltage | 600V |
| MPPT Voltage Range | 80V-550V |
| Rated MPPT Voltage | 360V |
| Max. Input Current | 6*17A |
| Max. PV Short-Circuit Current | 6*23A |
| MPP Tracker/No. of Strings per MPP Tracker | 6/1 |
| Dimensions (WxHxD) | 600W*145H*280D (mm) |
Expansion Battery
Interface Description

| Item | Description |
|---|---|
| A | Expansion Battery Power Button |
| B | Expansion Battery Output Port |
| C | Expansion Battery Breaker |
Specification
| Model | GIV-BAT-13.5-AIO2-E |
|---|---|
| Battery Type | LFP |
| Operating Voltage Range | 260~346 Vd.c. |
| Nominal Voltage | 307.2 Vd.c. |
| Max. Charging Current | 25A |
| Max. Discharging Current | 41A |
| Rated Capacity | 52Ah |
Gateway 2
Interface Description

| Item | Description | Item | Description |
|---|---|---|---|
| A | Gateway 2 Status Light | H | Communication Port |
| B | Grid Port | I | USB Port |
| C | M25 Wire Port | ||
| D | General Load Port | ||
| E | M32 Wire Port | ||
| F | M40 Wire Port | ||
| G | Communication Port |
Specification
| Model | GIV-AIO-GW1-2 (Gateway 2) |
|---|---|
| Grid Output AC | |
| Nominal AC Power | 23,000W |
| Nominal AC Current | 100A |
| Max. AC Current | 100A |
| Rated Voltage | 230V.a.c (180 to 270V.a.c) |
| Rated Grid Frequency | 50/60±5Hz |
| Max. Output Fault Current | 6000A |
| Max. Output Overcurrent Protection | 100A |
| General Load Output AC | |
| Nominal AC Power | 23000W |
| Nominal AC Current | 100A |
| Max. AC Current | 100A |
| Rated Voltage | 230V.a.c (180 to 270V.a.c) |
| Rated Grid Frequency | 50/60±5Hz |
| Max. Output Fault Current | 6000A |
| Max. Output Overcurrent Protection | 100A |
| Critical Load Output AC | |
| Nominal AC Power | 9200W |
| Nominal AC Current | 40A |
| Max. AC Current | 40A |
| Rated Voltage | 230V.a.c (180 to 270V.a.c) |
| Rated Grid Frequency | 50/60±5Hz |
| Max. Output Fault Current | 6000A |
| Max. Output Overcurrent Protection | 40A |
| Smart Load Output AC | |
| Nominal AC Power | 9200W |
| Nominal AC Current | 40A |
| Max. AC Current | 40A |
| Rated Voltage | 230V.a.c (180 to 270V.a.c) |
| Rated Grid Frequency | 50/60±5Hz |
| Max. Output Fault Current | 6000A |
| Max. Output Overcurrent Protection | 40A |
| Generator Input AC | |
| Nominal AC Power | 9200W |
| Nominal AC Current | 90A |
| Max. AC Current | 90A |
| Rated Voltage | 230V.a.c (180 to 270V.a.c) |
| Rated Grid Frequency | 50/60±5Hz |
| Max. Output Fault Current | 6000A |
| Max. Output Overcurrent Protection | 90A |
| EV Charger Output AC | |
| Nominal AC Power | 7200W |
| Nominal AC Current | 32A |
| Max. AC Current | 32A |
| Rated Voltage | 230V.a.c (180 to 270V.a.c) |
| Rated Frequency | 50/60±5Hz |
| Max. Output Fault Current | 6000A |
| Max. Output Overcurrent Protection | 32A |
| AIO 2 Input AC | |
| Nominal AC Current | 52A |
| Max. AC Current | 52A |
| Rated Voltage | 230V.a.c (180 to 270V.a.c) |
| Rated Frequency | 50/60±5Hz |
| PV Input AC | |
| Nominal AC Current | 43A |
| Max. AC Current | 43A |
| Rated Voltage | 230V.a.c (180 to 270V.a.c) |
| Rated Frequency | 50/60±5Hz |
| AIO 2 Parallel Input AC | |
| Nominal AC Current | 52A |
| Max. AC Current | 52A |
| Rated Voltage | 230V.a.c (180 to 270V.a.c) |
| Rated Frequency | 50/60±5Hz |
| General Data | |
| Dimensions | 380Wx460Hx150D (mm) |
| Protective Class | Class I |
| Operating Temperature Range | -20 ~ +50°C |
| Ingress Protection | IP65 |
| Monitoring Data | |
| Radio Type | 2.4G WiFi / BLE |
| Frequency Range | 2412-2472 MHz For WiFi 2402-2480 MHz For BLE |
| Transmit Power (EIRP) | WiFi: 17.68 dBm (EIRP) | WiFi: 15.46 dBm (EIRP) BLE: 2.41 dBm (EIRP) | BLE: 3.02 dBm (EIRP) |
| Radio Type | LTE/GNSS |
| Frequency Range | Band 1: 1920-1980 MHz; Band 3: 1710-1785MHz, Band 7: 2500-2570 MHz; Band 8: 880-915 MHz; Band 20: 832-862 MHz; Band 28: 703-748 MHz; GNSS: 1559-1610 MHz |
| Transmit Power (EIRP) | LTE Band 1/3/7/8/20/28: 23 dBm |
Key Features
- It supports multiple scenarios: grid-connected, off-grid, and pure off-grid. It also supports multiple working modes like spontaneous self-use (ECO Mode), Time of Use (TOU), and requires full Internet access for app integration.
- Users can query the total discharge information of the product’s life cycle in real time.
- It provides intelligent operation and is simple to setup and configure.
- It has built-in Wi-Fi and 4G for integrated connectivity.
- It operates independently with single-phase output to accommodate irregular load changes.
- It allows real-time adjustment of spontaneous self-consumption. You have full control of the output grid power.
- Modular terminals for system connections make installation and removal of individual components easier.
- The supporting battery has a modular design. You can freely match battery capacity.
- One person can install and operate the system.
- The factory settings meet the default settings of the main target market. Power can be generated by simply connecting the AC side and switching it on (Black Start)
- An LED display shows the real-time working status. You can use a mobile phone APP to control the system remotely.
Inverter Operating Modes
The inverter has several operating modes. The machine performs self-tests when first powered on. After the self-tests are normal, it enters an operating mode. The system will switch between modes and enter a standby state when a mode’s operation ends

| Item | Specification | Description |
|---|---|---|
| 1 | Standby Mode | The inverter is powered on but not actively charging or discharging.
|
| 2 | On-Grid Mode | The inverter is connected to the utility grid and operating normally.
|
| 3 | Off-Grid Mode | The inverter operates independently of the utility grid using battery and solar energy.
|
| 4 | Fault Mode | The inverter detects a fault and stops all operation to protect the system.
|
Main Work Modes
Daytime Mode
During daylight hours, the MPPT Unit receives energy from connected photovoltaic (PV) panels. The system prioritises energy usage in the following order:
- Supplies power to household loads.
- Charges the battery with surplus solar energy.
- Exports any remaining energy to the grid.
If the grid is unavailable, the generator can start automatically to power the system and recharge the battery if required.

Night-time Mode
During evening and night-time hours, the system discharges the battery to supply household loads, reducing reliance on the grid during peak electricity pricing. If needed, the battery may recharge during off-peak hours when tariffs are lowest.
If the battery is fully discharged, the system automatically switches to grid power. In the event of a grid outage, the generator can be started to power the home and recharge the battery.

Island Mode
The system can operate as an independent power system in island mode.
It can also be used as a backup power system if there is a power outage.
If there is no solar energy at this time, the generator can be started to power the entire household load. The generator can also charge the battery.

Demand Response Mode
(External Control by Grid supplier)
The system has a function for remote data collection and analysis. This can provide users with real- time information about the working situation of the entire system. If necessary, the system can also be controlled remotely to meet daily needs.
This mode requires integration with your chosen grid supplier that supports Grid Services

INSTALLATION
Unpacking Inspection
When you unpack the system, please check the following items:
- Ensure there are no missing accessories from the packaging list.
- Confirm the model and specification of the All in One, MPPT Unit, and Gateway1-2 nameplates match your order specifications.
- Make sure the packaging and product are free from any damage.
If any damage to the packaging is visible, or if you find that the unit is damaged after unpacking, please notify the distributor immediately. If anything is damaged or missing, please contact your supplier.
Do not dispose of the original packaging. If you need to transport the unit, it is better to store it in the original packaging.
Packaging List
All in One 2

| Item | Description | Amount |
|---|---|---|
| A | All in One | 1 |
| B | Wall Rack | 2 |
| C | Concrete Anchor | 4 |
| D | Safety Screw (Anti-Theft) | 2 |
| E | Antenna is Integral | 1 |
| F | Rawl Plug | 4 |
| G | Tapping Screw Coach Screw | 4 |
Gateway 2

| Item | Description | Amount |
|---|---|---|
| A | Gateway 2 | 1 |
| B | Wall Rack | 1 |
| C | Concrete Anchor | 4 |
| D | Coach Screw | 4 |
| E | WiFi Antenna | 1 |
| F | Rawl Plug | 4 |
| G | Torx Screw (Anti-Theft) | 2 |
MPPT Unit

| Item | Description | Amount |
|---|---|---|
| A | MPPT Unit | 1 |
| B | Stainless Screw | 6 |
Safety Instructions
![]() | DANGER - Risk of Death Due To Fire or Explosion.
|
![]() | WARNING - Risk of Burns Due To Hot Enclosure Parts.
|
![]() | CAUTION - Equipment Damage and Operational Risks.
|
![]() | NOTICE - Important Safety Information Regarding Voltage.
|
Mounting Area
Follow these recommendations when choosing an installation location:
- Do not install the product where it can come into direct contact with water or direct sunlight.
- The location must be able to support the weight and size of the inverter.
- Choose a location where you can easily see the product status display.
- Do not install the product on structures made of flammable or explosive materials.
- The humidity of the installation location should be between 0-95%, with no condensation.
- The installation location must be safely accessible at all times.
- Do not place anything on top of the product. This can cover the product and prevent proper cooling.
- Do not install the product near a TV antenna or any other antenna or antenna cable. To minimize the risk of interference.
- The product needs enough space for cooling. This provides good ventilation and ensures heat can be lost effectively.
- The surrounding air temperature should be below 40ºC for the best operation.
- When mounted, the product should be installed vertically, perpendicular to the horizontal ground.

Minimum Clearance
Please ensure that the All in One 2 meets the following clearance criteria:

Installation Procedure
All in One 2 and MPPT Unit (Desk)
Step 1: The wall must be at least 120mm deep. Use the support bracket as a template to mark the positions for drilling holes.

Step 2: Drill holes to a depth of at least 75mm. Hammer the expansion bolts into the holes. Fix the support bracket to the wall using the expansion bolts. Use appropriate fixings for the construction type.

Step 3: Open the All in One 2 packing case. Take out the battery module.

Step 4: Mount the All in One 2 unit onto the wall mount bracket. Please note, the All in One 2 can be wall mounted or floor standing but either configuration requires the bracket.

Step 5: Adjust the height of the support feet. Ensure that the top surface of the All in One 2 is level.

Step 6: Insert the battery module into the chassis of the All in One 2 battery compartment and install the internal battery front cover.

Step 7: Screw the front cover into place, ensuring it is fitted correctly so the LEDs can be seen correctly.

Step 8: Place the MPPT Unit on top of the All in One 2 unit.

Step 9: Fasten the MPPT Unit to the All in One 2 unit using screws.

Gateway 2
Step 1: The wall must be at least 120mm deep. Use the bracket as a template to mark the positions for drilling holes.

Step 2: Drill holes to a depth of no less than 75mm. Hammer the expansion bolts into the holes. Fix the support bracket to the wall using the expansion bolts.

Step 3: Hang the Gateway 2 unit on the support bracket.

Step 4: Fasten the Gateway 2 to the support bracket using screws. Ensure you leave enough space around the gateway unit for heat dissipation.

Electrical Connection
Inverter AC Connection
- The output power cable of the All in One 2 should be at least 10mm². Strip the insulation layer of the cable by 12mm. Route the power cable through the waterproof gland. Then, connect it to the AC Input WAGO block.
- PV power cables should be at least 4mm². For longer runs, use 6 mm² to reduce voltage drop.
- The cable length should not exceed 50m. The resistance of a longer cable will consume power and reduce the efficiency of the product.

Gateway 2 AC Connection

| Item | Description |
|---|---|
| A | Generator Connection |
| B | PV Inverter Connection |
| C | Parallel Connection |
| D | Critical Load |
| E | Smart Load |
| F | EV Charger |
| G | All in One Connection |
| H | General Load Connection |
| I | Bypass Breaker |
| J | Grid Connection |
A - Generator Connection
- The power cable specifications of the generator are determined by the output power of the generator.
- Connect the generator to the generator WAGO via a suitable over current protection device (not supplied); Max 32A

B - PV Inverter Connection
- The power cable specifications of the PV inverter are determined by the output power of the PV inverter.
- Connect the PV Inverter via a suitable overcurrent device to the WAGO marked PV Inverter.

C - Parallel Connection
- Up to 3× AIOs can be paralleled via the Gateway; connect each AIO to the Gateway with its own AC feed and RJ45 comms.
- Use either Gateway external tails or internal RCBOs (C32, bi-directional) for protection; ensure all AIOs run matching D612-A612 firmware and Gateway v10+ before commissioning.

D - Critical Load Connection
- The power cable for the critical load should be suitably sized based on the connected load and the overcurrent protection device used.
- The critical load should be connected to the marked WAGO via the overcurrent device (Not supplied) – Max 32A.

E - Smart Load
- The power cable for the smart load should be suitably sized according to the connected load and the overcurrent protection used.
- The smart load shall be connected to the WAGO marked Smart Load, via a suitable sized over current protection (Not supplied) – Max 32A.

F - EV Charger
- Connect the EV charger from a 40A Type A 30 mA RCD to the grid busbar using 6 mm² (or larger) cable; ensure the grid breaker is isolated before work.
- Please ensure that you fit the correct over current and residual current protection for the circuit inline with local wiring regulations.

G - All in One Connection
- Connect the AC supply from the All in One to the Gateway using the lower AC terminals; remove the bottom cover before wiring and replace once complete.
- Connect the communication cable from the All in One to the Gateway comms port as shown, ensuring correct routing through the lower entry points (detailed in Communication Connection).

H - General Load Connection
- The general load power cable should be at least 16mm typically 25mm fed via a suitable over current device.

H i) - General Load Connection Configuration
- General load can be configured to split essential backup loads powered through the Gateway 2 during outages, while non-essential loads remain connected to the main meter and are not backed up.

J - Grid Connection
- The grid power cable should be at least 25mm².
- Connect the grid supply to the supplied C100 breaker. Ensuring correct polarity is observed.

Communication Connection
System Communication Connection
- Connect the All in One 2 to Gateway communication cable to their respective ports using a fully wired screened RJ45 cable.
- Communication with the portal can be either 4G, WiFi or LAN.

Gateway 2 Communication Port

| Item | Function | Foot Position | Note |
|---|---|---|---|
| A | LAN Port | Standard RJ45 Port | |
| B | GPS Port | Antenna Connector | |
| C | 4G Port | Antenna Connector | |
| D | WiFi Port | Antenna Connector | |
| E | USB Extension Port | Four Pin Connector | |
| F | DRM Port | RJ45 Port for DRM | |
| G | All in One Port | RJ45 Port for AIO | |
| H | DO1 Port | 1:DO1+ 2:DO1- | Digital Output Port |
| I | Debug Port | ||
| J | DI1 | 1:DI1+ 2:DI1- | Digital Input Port |
| K | PV RS485 | ID1 Meter | |
| L | AC RS485 | ID2 Meter | ID3-8 can also be connected here |
All in One 2 Communication Port

| Item | Function | Foot Position | Note |
|---|---|---|---|
| A | Gateway Network Cable Port | Standard RJ45 Port | Gateway Communication Interface |
| B | Parallel In Port | Single All in One does not use this | |
| C | DRM Port | RJ45 Port for DRM | |
| D | DO1 and DO2 Output Port | 1:DO1+ 2:DO1- 3:DO2+ 4:DO2- | Digital Output Ports |
| E | DI1 and DI2 Input Port | 1:DI1+ 2:DI1- 3:DI2+ 4:DI2- | Digital Input Ports |
| F | BCU USB | ||
| G | LCD USB | Future Use | |
| H | 4G Antenna Port | Antenna Connector | |
| I | WiFi Antenna Port | Antenna Connector | |
| J | GPS Antenna Port | Antenna Connector | |
| K | LAN Port | Standard RJ45 Port | |
| L | Gateway Out Port | Single All in One does not use this | |
| M | Parallel Out Port | Single All in One does not use this | |
| N | 485 Port | ||
| O | Inverter Firmware Port | Standard USB Port | Single All in One does not use this |
| P | User C | ||
| Q | RS485 | ID1-8 Meter | For Gateway-less installations |
Wireless Connectivity
The All in One 2 uses a combination of 4G and WiFi as standard wireless communication. The inverter comes with internal Wi-Fi wireless communication and 4G modem. During set-up, the unit will default to 4G for set-up, with WiFi setup during commissioning. You can connect the corresponding communication connection to the monitoring server for real-time data monitoring and inverter control. For specifics, refer to the Wi-Fi configuration instructions or consult your installation supplier.
You may if required connect external antenna to these ports (not supplied).
DRM (Demand Response Management)
When the inverter is used in Australia, it needs to connect to a DRMS (Demand Response Management System) device. Connect the DRMS device to the DRM terminal of the inverter to run.
The RJ45 terminal is defined as follows:
| Pin | DRMS | Pin | DRMS |
|---|---|---|---|
| Pin1 (Orange-White) | DRM1/5 | Pin5 (Blue-White) | Ref/Gen |
| Pin2 (Orange) | DRM2/6 | Pin6 (Green) | GND |
| Pin3 (Green-White) | DRM3/7 | Pin7 (Brown-White) | / |
| Pin4 (Blue) | DRM4/8 | Pin8 (Brown) | / |
Inverter demand response modes:
| Mode | RJ45 Pins to be Connected | Demand |
|---|---|---|
| DRM0 | Connect Pin5 and Pin6 | Stop |
| DRM1 | Connect Pin1 and Pin5 | Disallow charge |
| DRM2 | Connect Pin2 and Pin5 | Charge power should be less than 50% of the rated power |
| DRM3 | Connect Pin3 and Pin5 | Charge power should be less than 75% of the rated power |
| DRM4 | Connect Pin4 and Pin5 | Charge power should be less than 100% of the rated power |
| DRM5 | Connect Pin1 and Pin5 | Disallow discharge |
| DRM6 | Connect Pin2 and Pin5 | Discharge power should be less than 50% of the rated power |
| DRM7 | Connect Pin3 and Pin5 | Discharge power should be less than 75% of the rated power |
| DRM8 | Connect Pin4 and Pin5 | Discharge power should be less than 100% of the rated power |
SYSTEM COMMISSIONING
System commissioning is a critical phase that ensures the All in One 2 system and its associated components are correctly configured and verified for safe and optimal operation before going live. This process must be performed by a qualified technician using the designated engineering software.
![]() | CAUTION - Commissioning Required
|
Pre-Commissioning Checks
Before initiating the software-based commissioning steps, conduct a thorough physical inspection and verification:
- Wiring: Check that all DC (PV, battery) and AC (grid, loads) wires are secure, correctly polarized, and match design plans. Look for loose connections or damaged insulation.
- Components: Ensure all parts (All in One 2, MPPT Unit, Gateway 2, battery, breakers) are correctly installed and undamaged.
- Earthing: Verify all components are correctly earthed.
- PV Array:
- Confirm PV string voltage (Voc) and current (Isc) are within limits for the All in One 2 and MPPT Unit.
- Ensure PV strings connect to the correct MPPT inputs. Observing correct polarity
- Ensure the PV Isolator(s) are switched on.
- Battery:
- Ensure any external battery expansion modules are correctly connected and switched on.
- AC Supply: Ensure grid voltage and frequency are within the inverter’s allowed range. Ensure the isolator is ON.
System Startup and Shutdown
![]() | WARNING - High Voltage Risk
|
Start-Up the Inverter
Follow these steps to start the inverter:
- Switch on the AC circuit breaker.
- Turn on the PV DC switch(s). Note there are 2 of them in the MPPT module (1-3 & 4-6)
- Turn on the battery breaker. Including expansion packs
- The inverter will start automatically if all the following conditions are met:
- The PV voltage is higher than 80V on at least one string.
- The battery voltage is higher than 254.4V.
- The AC supply is switched on.
Disconnect the Inverter (Shutdown)
Follow these steps to shut down the inverter:
- Disconnect the AC circuit breaker to prevent it from being reactivated.
- Disconnect the Battery breaker to prevent it from being reactivated.
- Turn off the PV switch(s).
- Check the inverter operating status. It may remain on for up to 5 mins
- Wait until the LED display has gone out; the inverter is now shut down.
Equipment Parameter Setting and Monitoring
You can perform the following operations for the inverter using the designated software or monitoring platforms:
- View the running data, software version, and alarm information of the device.
- Set the equipment parameters, such as power grid parameters, communication parameters.
- Maintain the equipment.
- Upgrade the device software version.
MAINTENANCE
System Power-Off for Maintenance
Before performing any maintenance, you must completely power off the system:
- Disconnect the AC circuit breaker to prevent it from reactivating.
- Disconnect the battery circuit breaker to prevent it from reactivating.
- Turn off the photovoltaic (PV) switch(s).
- Check the operating status of the inverter.
- Wait until the LED display goes out and the inverter turns off.
![]() | CAUTION - Ensure System is Fully switched off and Cool
|
Regular Maintenance
- Checking Heat Dissipation
If the inverter regularly reduces its output power due to high temperatures, please improve the heat dissipation conditions. You may need to clean the heat sink or check for other obstructions that block airflow. Check the area for debris and accumulated dust. - Cleaning the Inverter
If the inverter is dirty, please shut down the inverter completely as described previously. Then, clean the enclosure lid. Use a soft, dry cloth. If necessary, you can use a slightly damp cloth. Do not use harsh chemicals or abrasive cleaners. - Checking the DC switch
Check for externally visible damage and discoloration of the DC breaker and its cables at regular intervals. If there are any signs of visible damage to the breaker, or visible discoloration or damage to the cables, contact the installer immediately.
![]() | NOTICE - Maintain DC Switch Contacts
|
- Fan Maintenance
Inspect the fan for dust, noise, or obstructions. Clean gently using a soft brush or compressed air. Do not use liquids. Replace if faulty.
TROUBLESHOOTING
GivEnergy products undergo strict testing and inspection before delivery to ensure high performance and reliability. However, as with all electrical devices, issues may still occur.
If you experience any problems, visit www.givenergy.co.uk check the Q&A section, or contact GivEnergy Customer Support for further assistance.
To ensure a quick and efficient resolution, please have the following details ready when contacting support:
- Product Serial Number(s): Located on the product label(s) of the All in One 2 and any connected GivEnergy components (e.g., MPPT Unit, Gateway 2).
- Error Code or System Message: Note any error codes or messages displayed on the unit or in the monitoring app.
- Installation Date and Details: Include the date of installation and basic system configuration.
- Description of the Issue: Clearly explain the problem, when it started, and how it affects system operation.
- System Readings (if safely accessible):
- Battery Voltage
- Grid Voltage and Frequency
- PV Voltage (if applicable)
- Time of Fault Occurrence: Note the specific date and time when the issue first appeared or typically occurs.
- Reproducibility: Can you reliably recreate the issue, or does it happen randomly?
- Recent Changes: Note any recent changes to the system, electrical setup, or significant weather events.
This section provides suggestions for common faults.
| No. | Fault Name | Reason of Fault | Handling Suggestions |
|---|---|---|---|
| 1 | Inverter NTC Fault | The inverter’s working environment temperature is too high or too low. | If temperature is too high: Lower the ambient temperature or turn off the inverter for 15 minutes, then restart. Ensure installation follows the user manual guidelines. If temperature is too low: Do not attempt to start the inverter. Contact after-sales service immediately. |
| 2 | Grid Frequency Fault | The inverter detects that the grid frequency is outside the normal range specified by safety regulations. | Verify that the Grid Code (Grid Safety Standard) is correctly configured. Check if the AC frequency (Freq) is within the acceptable range. If the issue is rare and resolves quickly, it may be due to occasional grid instability. |
| 3 | Grid Voltage Fault | The inverter detects that the AC voltage is outside the normal range required by safety regulations. | Make sure the safety country setting of the inverter is correct. Use a multimeter to check whether the AC voltage between the L line and N line is within the normal range. If the AC voltage is too high, check local supply voltages and contact the supplier if the voltage exceeds normal values. If the AC voltage is too low, ensure the AC cable is properly connected and that the insulation is not compressed into the AC terminal. Ensure a suitable sized cable was used to connect the mains supply Make sure the grid voltage in your area is stable. |
| 4 | PV Voltage Fault | The inverter has detected that the PV voltage is outside the normal range of the rated requirements. | Turn off the PV switch and use a multimeter to check whether the open circuit voltage of the panel is below 600V. If the voltage is too high, reduce the number of connected panels to lower the input voltage. |
| 5 | DCI High | The inverter has detected a high DC component in the AC output. | Try restarting the inverter and check if the fault still exists. If the fault persists, contact after-sales service immediately. |
| 6 | Current Leak High | A ground fault may be caused by improper AC side N-line connection or high humidity. | Use a multimeter to check the voltage between the inverter and the grounded frame. The voltage should be close to 0V. If voltage is detected, check that the N wire and ground wire on the AC side are properly connected. If this failure occurs in the early morning, dawn, or rainy days, it may be due to temporary high humidity and should resolve on its own. |
| 7 | PV Isolation | Possible poor grounding of photovoltaic panels, aging PV panels, damaged DC cables, or high humidity. | Use a multimeter to check that the resistance between the inverter and the grounded frame is close to zero. If not, check the system wiring. If humidity is too high, isolation failure may occur temporarily. Check the resistance of PV1+/PV2+/ BAT+/PV- to ground. If it is below 30kΩ, verify system wiring. Restart the inverter and check if the fault still exists. If the issue persists, contact after-sales service. |
| 8 | No Utility | The inverter does not detect grid information. | Use a multimeter to check whether there is voltage on the AC side. Ensure the grid voltage is normal. Check that the AC cable is firmly connected and not loose. If everything is fine, try disconnecting the AC circuit breaker and reconnecting it after 5 minutes. |
| 9 | Bus Over Voltage | The internal BUS voltage is out of range | Restart the inverter. If the fault still exists, contact after-sales service. |
| 10 | DSP Communication Fault | Caused by strong external magnetic field interference | Restart the inverter. If the fault persists, contact after-sales service. |
| 11 | Hall Sensor Fault | HCT detection failure in the system | Contact after-sales service. |
| 12 | GFCI Fault | Abnormal Ground Fault Circuit Interrupter (GFCI) detection | Contact after-sales service. |
| 13 | Relay Fault | The neutral and ground wires on the AC side are not properly connected or are intermittently faulty | Check with a multimeter whether the voltage between N and ground is below 10V. If voltage is higher, confirm that the N and ground wires are correctly connected. Restart the inverter if necessary. |
| 14 | EEPROM Fault | Caused by external strong magnetic field interference | Restart the inverter. If unresolved, contact after-sales service. |
| 15 | Consistent Fault | The internal programs of the system do not match | Restart the inverter. If the fault persists, contact after-sales service. |
| 16 | ARM Communication Fault | Caused by strong external magnetic field interference | Restart the inverter. If the fault persists, contact after-sales service. |
| 17 | Back-Up Overload Fault | Total backup load exceeds the rated output power | Reduce the off-grid loads to keep total power below the rated output. |
| 18 | BMS Comm Fault | The inverter and lithium-ion battery communication is abnormal | Power off the inverter and check the BMS cable connection. If unresolved, contact after-sales service. |
| 19 | Bat Volt Low | Lithium battery voltage is below 196V Lead-acid battery voltage is below (LV- cell × 1V) | Confirm that the battery connection cable is securely attached. Ensure that the battery is switched on and the LED is lit. Check that the battery is not over-discharged. If it is, enable forced charging in the inverter settings to recover the battery after power replenishment.Or Use Activate Battery setting to wake and charge a very low battery. If the issue persists, contact the dealer or after-sales service. |
| 20 | Bus Unbalance Fault | The positive and negative Bus voltage difference exceeds 70V | Contact after-sales service. |
| 21 | Meter Comm Loss | The inverter is not communicating properly with the meter | Check that the meter and inverter are correctly connected. Ensure that the RX/TX communication lines are not reversed. Ensure you are using a single pair of wires, Belden RS485 cable is best. |
| 22 | Battery Need Charge | The battery voltage is too low to discharge | Charge the battery from the AC supply. |
SYSTEM REMOVAL AND DISPOSAL
Remove Machine
Follow the shutdown procedure described in section “Disconnect the Inverter (Shutdown)“ to disconnect the inverter completely.
Dismantling the inverter:
- Ensure the inverter is fully disconnected and powered down.
- Remove all connection cables from the inverter.
- Unscrew and remove all projecting cable glands.
- Remove batteries from the Inverter.
- Carefully lift the inverter off its mounting bracket.
- Unscrew and remove the bracket screws from the wall.
![]() | CAUTION - Ensure System is Fully Shut Down and Cool
|
Scrap Machine (Disposal)
When the inverter can no longer be used and needs to be scrapped, please dispose of it according to the electrical waste disposal requirements of your country or region. You can contact your dealer or the customer service center for consultation and disposal.
![]() | NOTICE - Proper Disposal Required
|
Contact
| Phone | |
| https://predbat-help.freshdesk.com/support/tickets/new | |
| Website | https://predsupport.com/ |
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article